CA738

CAST Sounder Control Module

Trade Price

£84.36

Per

1

Unit

EACH

Pack Quantity

CA738

Information

Allows a zone/circuit of conventional fire alarm sounders to be connectedto a CAST protocol fire alarm system. Onboard short circuit loop isolator. Conventional sounder circuit is continually monitored for open and short circuit faults. 3mA typical alarm current (530uA typical quiescent current) @ 22-40V DC. Can provide up to 50mA output current (taken from the CAST addressable loop). Polling, sounder circuit active and sounder circuit fault indicators. ‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Now available to purchase, its key features include: * 255 devices per loop. * Autonomous decision-making for faster response times. * Multiple type codes. * 40V loop drive voltage. * Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer. * Powerful multi-level addressing facilitates easy device addition and swapped device identification. * Multiple functionality at a single address (integrated devices) – coming soon. * Volumes, tones & detector modes can be changed at compatible panels. * High-speed data transmission and robust data transfer. * Intrinsically EN54-13 compliant. * Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device). * Replace device function. * Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs. * Designed and manufactured in the UK.

Technical Specifications

Compatibility

Compatible with C-TEC's XFP/ZFP CAST Addressable Fire Panels.

Application/operation

Allows a zone/circuit of conventional fire alarm sounders and visual alarm devices to be connected to a CAST compatible fire alarm system.

Supply/operating voltage

22-40V DC

Quiescent current

530uA typical.

Zone current

Can provide up to 50mA (taken from the CAST addressable loop)

Alarm current

3mA @ 22-40V DC.

Indicators

Polling, sounder circuit active and sounder circuit fault indicators.

Product dimensions (mm)

147 W x 87H x 22 D mm. Can be mounted on a standard 25mm UK flush or surface double gang back box.

IP Rating

IP40 when correctly installed.

Weight

122g.

Document Links

Catalogue page

Datasheet