Trade Price
£294.11
Per
1
Unit
EA
Pack Quantity
1
Product name
SE7000 Series
Device short name
SE7200
Product or component type
Zone controller
Device application
Zone thermostat
Net weight
0.34 kg
AWG gauge
AWG 22...AWG 18
height
124.97 mm
Width
86.87 mm
Directives
89/336/EEC - electromagnetic compatibility
Depth
29.97 mm
Ambient air temperature for operation
-0…50 °C
Market segment
Residential
Ambient air temperature for storage
-30…50 °C
Measurement accuracy
Temperature: +/- 0.9 °F, (at 70 °F typically calibrated)
Product certifications
FCC conforming to CFR 47 part 15 class A CE C-Tick conforming to AS/NZS CISPR 22 UL listed file E27734 CCN XPAX UL listed file E27734 CCN XPAX7
Information displayed
Temperature: - 40...122 °F
Network frequency
60 Hz 50 Hz
Communication port protocol
BACnet MS/TP
Input voltage
0…10 V DC
Temperature setting range
4…32 °C heating -17 °C per step 12…38 °C cooling
Input type
2 x universal
Output type
2 xuniversal 1 xanalog
Standards
ICES-003 UL 873 FCC part 15 Subpart B CSA C22.2 No 24
[Us] rated supply voltage
10...30 V AC 50/60 Hz
Sensor type
10 kOhm T2 NTC thermistor
Output voltage
0...10 V DC
Relative humidity
0…95 % RH, non-condensing
Output current
<= 5 mA
Range
EcoStruxure Building Expert
Economizer
No
Humidity control
No
PIR cover
No
Scheduling
No
Device presentation
Without cover
Number of steps
3
Rated operational power in VA
2 VA
Connections - terminals
Screw terminal
Regulation loop
For heating: adjustable P regulator by -16 °C (factory settting) For cooling: adjustable P regulator by -16 °C (factory settting)
Range compatibility
EcoStruxure Building Expert communication card EcoStruxure Building Expert sensor EcoStruxure Building Expert temperature sensor EcoStruxure Building Expert relay EcoStruxure Building Expert sensor coverplate
Electrical insulation class
Class II
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
10.0 cm
Package 1 Width
15.0 cm
Package 1 Length
5.0 cm
Package 1 Weight
200.0 g
Warranty
18 months
Datasheet