Trade Price
£491.12
Per
1
Unit
EA
Pack Quantity
1
SE8300 Series room controllers are used for Low Voltage Fan Coil Unit control. The room controllers rated supply voltage range is 24 to 28V AC at 50 or 60Hz +/-15%. The rated current is 4A. The device consumption is up to 12VA. The room controller is colored white and is equiped with a communication port that uses BACnet MS/TP protocol and a PIR sensor. Its Room and Outdoor Air Temperature Display Range is between -40 and 50 oC. The measurement accuracy is +/- 0.5%. The temperature setting range is 12 to 37.5oC for cooling and 4.5 to 32 oC for heating. The room controller is equiped with 2 digital inputs, 5 analog inputs (5 to 10V), 4 analog outputs, and 5 digital outputs. The analog output voltage is 0 to 10V DC at < 5mA into > 2 kOhm resistance. The digital output rating is 28V AC 50 or 60 Hz, 0.3A, 1.5A inrush current. The product follows the following standards: IEC 61326-1: 2005, FCC part 15 subpart C, RSS 210 issue 8, FCC part 15 subpart B, ICES-003, EN 60950-1: 2006/A2, EN 60950-1: 2013, ETSI EN 301 489-1: v1.9.2. The product follows the directives: 2014/30/EU - electromagnetic compatibility, 2014/35/EU - low voltage directive, 2014/53/EU - radio equipment directive. The ambient air temperature for operation is between 0 and 50oC. The relative humidity for operating or storage is between 0 and 75% non condensing. The humidity reading range is 10 to 90% RH non-condensing.
Product name
SE8000 Series
Device short name
SE8300
Product or component type
Room controller
Device application
Low voltage fan coil
Net weight
340 g
AWG gauge
AWG 24...AWG 18
Targeted region
North America.
Height
120 mm
Width
86 mm
Temperature resolution
0.1 °C
Humidity measurement drift
Less than 1 % yearly
Directives
2014/30/EU - electromagnetic compatibility 2014/35/EU - low voltage directive 2014/53/EU - radio equipment directive
[In] rated current
4 A
Depth
25 mm
Ambient air temperature for operation
0…50 °C
Market segment
Lodging/hotel Small commercial Buildings Healthcare Non-critical buildings Office Residential School
Housing colour
White
Ambient air temperature for storage
-30…50 °C
Measurement accuracy
Temperature: +/- 0.5 °C, Humidity: +/- 5 %, 20...80 % RH (non-condensing) Humidity: +/- 10 %, 10...20 % (non-condensing) Humidity: +/- 10 %, 80...90 % (non-condensing)
Information displayed
Temperature: - 40...122 °F
Network frequency
50 Hz 60 Hz
Communication port protocol
BACnet MS/TP Modbus RTU
Input voltage
0...10 V DC
Temperature setting range
12…37.5 °C cooling 4.5…32 °C heating
Calibration certificate
1 pt
Output voltage
24 V AC for relay output 0...10 V DC for analog output
Relative humidity
0…95 %
Output current
1 A relay output 3 A relay output (inrush) 0.3 A universal output 1.5 A universal output (inrush)
Input type
2 x dry contact 5 x analog
Sensor type
10 kOhm T2 NTC thermistor temperature Space RH sensor humidity Bulk polymer humidity
Output type
5 xrelay output 4 xuniversal
[Us] rated supply voltage
24 V AC 50/60 Hz +/- 15 %
Standards
EN/IEC 60730-1 FCC part 15 Subpart B ICES-003 ETSI EN 300 328 ETSI EN 301 489-1:v1.9.2 FCC part 15 Subpart C UL 60730-2-9 ETSI EN 301 489-17:v2.2.1, 2012
Humidity setting range
30…95 %
Range
EcoStruxure Building Expert
Economizer
Yes
Humidity control
Yes
PIR cover
No
Scheduling
No
Surface finish
Matt
Surface treatment
Untreated
Function available
Fan control HVAC control Available with CO2/RH/T Brightness sensor Changes can be made directly over display Code lock function Easily configurable Firmware update by USB
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
30.5 cm
Package 1 Width
21.8 cm
Package 1 Length
6.4 cm
Package 1 Weight
242 g
Warranty
18 months
Datasheet