3WL1220-3DG46-1BA4-Z

withdrawable circuit breaker with guide frame 4-pole, size II, IEC In=2000A to 690V, AC50/60Hz Icu=80kA at 500V rear connection horizontal Overcurrent release ETU 27 LSING protection adjustable 0.4-1 in Ground fault/N protection integrated With manual operating mechanism with storage with mechanical request With 1st auxiliary release Shunt release "F", F1 24 V DC; 100% ON period without 2nd auxiliary release 4NO+4NC A08= Tin plating of customer terminals in slide-in unit frame for horizontal connection or flange connection F23= Internal current converter 4-pole switch BGII R10= Arc chute cover On not possible with option A05 Rated voltage 1000 V R21= Shutter 2-part can be locked with bracket lock

Trade Price

£13,026.64

Per

1

Unit

EACH

Pack Quantity

1

Document Links

Datasheet