3WL1106-2CB36-6BJ4-Z

withdrawable circuit breaker with guide frame 3-pole, size I, IEC In=630A to 690V, AC50/60Hz Icu=55kA at 500V rear connection horizontal Overcurrent release ETU 25 LSI protection adjustable 0.4-1 in Motorized/manual operating mechanism with spring charging motor 24-30 V DC Activation 24 V DC With 1st auxiliary release Shunt release "F", F1 24 V DC; 100% ON period With 2nd auxiliary release "R", F3 Undervoltage, instant. 24 V DC 4NO+4NC B06= Rated current reference module 630 A for ETU25, 27, 45, 55, 75, 76 for setting rated current in K07= Tripped signaling contact, 1 CO not possible with option F02 R21= Shutter 2-part can be locked with padlock T40= Door sealing frame

Trade Price

£5,761.40

Per

1

Unit

EACH

Pack Quantity

1

Document Links

Datasheet