1SFL527002R1411

AF205-30-11-14 250-500V50/60HZ-DC

Trade Price

£884.62

Per

1

Unit

EA

Pack Quantity

1

1SFL527002R1411

Information

AF190...AF370 3 Pole contactors - 55 to 200kW AC/DC operated 1NO+1NC aux * Part number: AF205-30-11-14 * AF146.AF370 contactors are mainly used for controlling 3-phase motors and power circuits up to 1000V AC. * Control circuit: AC or DC operated with electronic coil interface accepting a wide control voltage range (e.g. 100...250 V AC and DC), only 4 coils to cover control voltages between 24...500 V 50/60 Hz and 20...500 V DC - can manage large control voltage variations - reduced panel energy consumption - very distinct closing and opening - can withstand short voltage dips and voltage sags (SEMI F47 conditions of use on request). * Built-in surge suppression * Add-on auxiliary contact blocks for side mounting and a wide range of accessories

Technical Specifications

Minimum Order Quantity

1 piece

Customs Tariff Number

85364900

Product Net Width

105 mm

Product Net Depth / Length

152 mm

Product Net Height

196 mm

Product Net Weight

2.4 kg

Number of Main Contacts NO

3

Number of Main Contacts NC

0

Number of Auxiliary Contacts NO

1

Number of Auxiliary Contacts NC

1

Rated Operational Voltage

Main Circuit 1000 V

Rated Frequency (f)

Main Circuit 50 / 60 Hz

Conventional Free-air Thermal Current (Ith)

acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 350 A

Rated Operational Current AC-1 (Ie)

(1000 V) 40 °C 275 A(1000 V) 55 °C 250 A(1000 V) 60 °C 250 A(1000 V) 70 °C 200 A(690 V) 40 °C 350 A(690 V) 55 °C 300 A(690 V) 70 °C 240 A

Rated Operational Current AC-3 (Ie)

(415 V) 55 °C 205 A(440 V) 55 °C 205 A(500 V) 55 °C 186 A(690 V) 55 °C 165 A(1000 V) 55 °C 100 A(380 / 400 V) 55 °C 205 A(220 / 230 / 240 V) 55 °C 205

Rated Operational Power AC-3 (Pe)

(415 V) 110 kW(440 V) 132 kW(500 V) 132 kW(690 V) 160 kW(1000 V) 132 kW(380 / 400 V) 110 kW(220 / 230 / 240 V) 55 kW

Rated Breaking Capacity AC-3

8 x Ie AC-3

Rated Making Capacity AC-3

10 x Ie AC-3

Short-Circuit Protective Devices

gG Type Fuses 400 A

Rated Short-time Withstand Current Low Voltage (Icw)

at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1640 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 350 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 670 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2050 Aat 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 947 A

Maximum Breaking Capacity

cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 3500 Acos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2500 A

Maximum Electrical Switching Frequency

(AC-1) 300 cycles per hour(AC-2 / AC-4) 150 cycles per hour(AC-3) 300 cycles per hour

Rated Operational Current DC-1 (Ie)

(110 V) 2 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 40 °C 275 A

Rated Operational Current DC-3 (Ie)

(110 V) 2 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 40 °C 275 A

Rated Operational Current DC-5 (Ie)

(110 V) 2 Poles in Series, 40 °C 275 A(220 V) 3 Poles in Series, 40 °C 275 A

Rated Insulation Voltage (Ui)

acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 Vacc. to UL/CSA 600 V

Rated Impulse Withstand Voltage (Uimp)

Main Circuit 8 kV

Mechanical Durability

5 million

Maximum Mechanical Switching Frequency

300 cycles per hour

Coil Operating Limits

(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ <= 70 °C)

Rated Control Circuit Voltage (Uc)

50 Hz 250 ... 500 V60 Hz 250 ... 500 VDC Operation 250 ... 500 V

Coil Consumption

Holding at Max. Rated Control Circuit Voltage 50 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 16.1 V·AHolding at Max. Rated Control Circuit Voltage DC 3.9 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 260 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 260 V·APull-in at Max. Rated Control Circuit Voltage DC 230 W

Operate Time

Between Coil De-energization and NO Contact Opening 37 ... 47 msBetween Coil Energization and NO Contact Closing 25 ... 55 ms

Connecting Capacity Main Circuit

Flexible 2 x 50 ... 95 mm²Rigid Al-Cable 1 x 95 ... 185 mm²Rigid Cu-Cable 2 x 50 ... 120 mm²

Connecting Capacity Auxiliary Circuit

Flexible with Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 2 x 1 .... 4 mm²

Degree of Protection

acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00

Terminal Type

Main Circuit: Bars

Maximum Operating Voltage UL/CSA

Main Circuit 1000 V

General Use Rating UL/CSA

(600 V AC) 300 A

Horsepower Rating UL/CSA

(200 V AC) Three Phase 60 hp(208 V AC) Three Phase 60 hp(220 ... 240 V AC) Three Phase 75 hp(440 ... 480 V AC) Three Phase 150 hp(550 ... 600 V AC) Three Phase 200 hp

Ambient Air Temperature

Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... 50 °CClose to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... 70 °CClose to Contactor for Storage -40 ... 70 °C

Maximum Operating Altitude Permissible

Without Derating 3000 m

RoHS Status

Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

ABB EcoSolutions

Yes

Circular Design Principles Recyclability Rate

Design for Closing Resource Loops - Standard EN45555 - 79.2 %

Group Waste to Landfill Target

Non-hazardous waste is sent to a landfill, where there is no alternative option available within 100km of a facility

Improved Resource Efficiency for Customers

Product Efficiency - Product requires less energy to operate compared to similar product on market or older products from the same line

Sustainable Material Content

Recycled Metal - 35 %

Package Level 1 Units

box 1 piece

Package Level 1 Width

160 mm

Package Level 1 Depth / Length

258 mm

Package Level 1 Height

235 mm

Package Level 1 Gross Weight

3 kg

Package Level 1 EAN

7320500480571

Object Classification Code

Q

ETIM 4

EC000066 - Magnet contactor, AC-switching

ETIM 5

EC000066 - Magnet contactor, AC-switching

ETIM 6

EC000066 - Power contactor, AC switching

ETIM 7

EC000066 - Power contactor, AC switching

ETIM 8

EC000066 - Power contactor, AC switching

eClass

V11.0 : 27371003

UNSPSC

39121529

IDEA Granular Category Code (IGCC)

4758 >> Iec Contactors

E-Number (Finland)

3706465

E-Number (Norway)

4117645

E-Number (Sweden)

3210148

Document Links