Eaton Moeller series NZM - Molded Case Circuit Breaker. Molded Case Switch, 3p, 800A
Product Length/Depth
401 mm
Product Height
207 mm
Product Width
210 mm
Product Weight
21 kg
Compliances
RoHS conform
Certifications
Specially designed for North America
CE marking
IEC
IEC 60947-2
UL 489
UL/CSA
CSA (Class No. 4652-06)
CSA-C22.2 No. 5-09
UL (Category Control Number WJAZ)
UL (File No. E148671)
CSA certified
CSA (File No. 22086)
UL listed
Rated operational current for specified heat dissipation (In)
800 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 690 V, 50/60 Hz
18 kA
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
DIN rail (top hat rail) mounting optional
Fixed
Built-in device fixed built-in technique
Amperage Rating
800 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Terminal capacity (copper strip)
Min. 6 segments of 16 mm x 0.8 mm at flat conductor terminal
Max. 10 segments of 32 mm x 1 mm (2x) at flat conductor terminal
10 segments of 50 mm x 1 mm (2x) at 1-hole module plate
Min. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
Max. 10 segments of 50 mm x 1 mm (2x) at rear-side connection (punched)
10 segments of 80 mm x 1 mm (2x) at rear-side width extension
NA: same as for IEC
Handle type
Rocker lever
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Ambient storage temperature - min
40 °C
Rated current (Iu)
1200 A
Terminal capacity (copper busbar)
M10 at rear-side screw connection
Min. 25 mm x 5 mm direct at switch rear-side connection
Max. 50 mm x 10 mm (2x) direct at switch rear-side connection
Min. 25 mm x 5 mm at rear-side 1-hole module plate
Max. 50 mm x 10 mm (2x) at rear-side 1-hole module plate
50 mm x 10 mm (2x) at rear-side 2-hole module plate
Min. 60 mm x 10 mm at rear-side width extension
Max. 80 mm x 10 mm (2x) at rear-side width extension
NA: same as for IEC
10.8 Connections for external conductors
Is the panel builder's responsibility.
Special features
IEC/EN 60947-2: circuit breakers without overcurrent (CBI-X) with main switch characteristics and isolating characteristics to IEC/EN 60204.Rated current = rated uninterrupted current: 800 A
Ambient operating temperature - max
70 °C
Position of connection for main current circuit
Front side
Rated insulation voltage (Ui)
1000 V AC
Terminal capacity (copper stranded conductor/cable)
50 mm² - 240 mm² (4x) at 4-hole tunnel terminal
120 mm² - 185 mm² (1x) direct at switch rear-side connection
50 mm² - 185 mm² (4x) direct at switch rear-side connection
Min. 120 mm² - 300 mm² (1x) at rear-side 1-hole module plate
Max. 95 mm² - 300 mm² (2x) at rear-side 1-hole module plate
Min. 95 mm² - 185 mm² (2x) at rear-side 2-hole module plate
Max. 35 mm² - 185 mm² (4x) at rear-side 2-hole module plate
300 mm² (4x) at rear-side width extension
95 mm² - 240 mm² (6x) at rear-side width extension
NA: AWG 0- kcmil 500 (4x) at 4-hole tunnel terminal
NA: kcmil 250 - kcmil 350 (1x) direct at switch rear-side connection
NA: AWG 0 - kcmil 350 (4x) direct at switch rear-side connection
NA: min. kcmil 250 - kcmil 600 (1x) at rear-side 1-hole module plate
NA: max. AWG 3/0 - kcmil 600 (2x) at rear-side 1-hole module plate
NA: min. AWG 3/0 - kcmil 350 (2x) at rear-side 2-hole module plate
NA: max. AWG 2 - kcmil 350 (4x) at rear-side 2-hole module plate
NA: kcmil 600 (4x) at rear-side width extension
NA: AWG 3/0 - kcmil 500 (6x) at rear-side width extension
Features
Motor drive optional
Protection unit
Lifespan, electrical
2000 operations at 690 V AC-1
2000 operations at 415 V AC-3
3000 operations at 400 V AC-1
1000 operations at 690 V AC-3
2000 operations at 415 V AC-1
2000 operations at 400 V AC-3
Electrical connection type of main circuit
Screw connection
Short-circuit total breaktime
< 25 ms (≦ 415 V); < 35 ms (> 415 V)
Rated impulse withstand voltage (Uimp) at main contacts
8000 V
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
35 kA
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Three-pole
Switch positions
I, +, 0
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Equipment heat dissipation, current-dependent
71.04 W
Instantaneous current setting (Ii) - min
25000 A
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 230 V, 50/60 Hz
43 kA
Application
Branch circuits, feeder circuits
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Current rating (Iu) (UL 489 csa 22.2 no. 5.1)
1200 A
Rated short-circuit making capacity Icm at 240 V, 50/60 Hz
187 kA
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 440 V, 50/60 Hz
33 kA
Degree of protection (IP), front side
IP40 (with insulating surround)
IP66 (with door coupling rotary handle)
Rated short-circuit making capacity Icm at 525 V, 50/60 Hz
84 kA
Rated short-circuit making capacity Icm at 690 V, 50/60 Hz
74 kA
Instantaneous current setting (Ii) - max
25000 A
Overload current setting (Ir) - min
0 A
Short delay current setting (Isd) - min
0 A
Number of auxiliary contacts (normally closed contacts)
0
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Lifespan, mechanical
10000 operations
Overload current setting (Ir) - max
0 A
Voltage rating
690 V - 690 V
Degree of protection (terminations)
IP00 (terminations, phase isolator and band terminal)
IP10 (tunnel terminal)
Terminal capacity (aluminum stranded conductor/cable)
Min. 185 mm² - 240 mm² (1x) at rear-side 1-hole module plate
Max. 70 mm² - 185 mm² (2x) at rear-side 1-hole module plate
50 mm² (4x) at rear-side 2-hole module plate
240 mm² (2x) at rear-side width extension
70 mm² - 240 mm² (6x) at rear-side width extension
NA: aluminum conductor not applicable
Rated operating voltage Ue (UL) - max
600 V
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Short-circuit release non-delayed setting - min
25000 A
Degree of protection
IP20
In the area of the HMI devices: IP20 (basic protection type)
Overvoltage category
III
Short delay current setting (Isd) - max
0 A
Rated impulse withstand voltage (Uimp) at auxiliary contacts
6000 V
Number of auxiliary contacts (change-over contacts)
0
Ambient storage temperature - max
70 °C
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 525 V, 50/60 Hz
20 kA
Optional terminals
Connection on rear. Strip terminal. Tunnel terminal
Pollution degree
3
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Functions
Disconnectors/main switches
Short-circuit release non-delayed setting - max
25000 A
Rated short-circuit making capacity Icm at 400/415 V, 50/60 Hz
154 kA
Standard terminals
Screw connection
Optional:Tunnel terminal
Rear-side connection
Strip connection
Type
Switch-disconnector
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Rated short-circuit making capacity Icm at 440 V, 50/60 Hz
143 kA
Number of auxiliary contacts (normally open contacts)
0
Number of operations per hour - max
60
Circuit breaker frame type
N4
Direction of incoming supply
As required
Datasheet