NZM3-XA-230AC-MNS

Special voltage release

Trade Price

£124.83

Per

1

Unit

EACH

Pack Quantity

NZM3-XA-230AC-MNS

Information

Eaton Moeller series NZM - Molded Case Circuit Breaker. Shunt release, 230VAC, for mesh network, size 3

Technical Specifications

Product Length/Depth

42 mm

Product Height

90 mm

Product Width

30 mm

Product Weight

0.064 kg

Compliances

IEC

RoHS conform

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Rated control supply voltage (Us) at AC, 50 Hz - min

230 V

10.4 Clearances and creepage distances

Meets the product standard's requirements.

Minimum command time - min

10 ms

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Rated control supply voltage (Us) at DC - min

0 V

Rated control supply voltage (Us) at AC, 50 Hz - max

230 V

Frequency rating

50 Hz / 60 Hz (shunt release)

10.8 Connections for external conductors

Is the panel builder's responsibility.

Minimum command time - max

15 ms

Special features

Shunt release for mesh network circuit-breakers in conjunction with NZM-XZM capacitor unit

Only for short-time operation with a maximum on-time = 1 s

Operating range 10 - 110 % Us

not UL/CSA approved

Rated control voltage 230 V AC

Cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XU... undervoltage release.

Intermittent operation guaranteed by series connection of an M22-(C)K10 make contact.

Voltage rating at AC (x Us) - min

.1

Rated control supply voltage (Us) at DC - max

0 V

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Rated control supply voltage

230 V AC

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Used with

NZM3(-4), N(S)3(-4)

Electric connection type

Screw connection

Voltage rating at AC (x Us) - max

1.1

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

Number of contacts (normally closed contacts)

0

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.

Voltage type

AC

Frame

NZM3

Reaction time

20 ms

Suitable for

Off-load switch

Current consumption - max

0.5 A

Rated control voltage (relay contacts)

230 V AC

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

Time on duty - max

1000 ms

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Undelayed short-circuit release - min

0 A

Rated control supply voltage (Us) at AC, 60 Hz - min

230 V

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Terminal capacity (solid/flexible conductor)

18 - 14 AWG (2x) for undervoltage releases, off-delayed

0.75 mm² - 2.5 mm² (1x) at shunt release with ferrule

0.75 mm² - 2.5 mm² (2x) at shunt release with ferrule

18 - 14 AWG (2x) at shunt release

18 - 14 AWG (1x) at shunt release

0.75 mm² - 2.5 mm² (1x) for undervoltage releases, off-delayed with ferrule

0.75 mm² - 2.5 mm² (2x) for undervoltage releases, off-delayed with ferrule

18 - 14 AWG (1x) for undervoltage releases, off-delayed

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Type

Accessory

Shunt release

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

Rated control supply voltage (Us) at AC, 60 Hz - max

230 V

Number of contacts (normally open contacts)

0

Undelayed short-circuit release - max

0 A

Number of contacts (change-over contacts)

0

Document Links