Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 630A, plug-in module

Technical Specifications

Product Length/Depth

335 mm

Product Height

215.2 mm

Product Width

140 mm

Product Weight

7.72 kg

Compliances

RoHS conform

Rated operational current for specified heat dissipation (In)

630 A

10.11 Short-circuit rating

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Instantaneous current setting (Ii) - max

6930 A

10.4 Clearances and creepage distances

Meets the product standard's requirements.

10.12 Electromagnetic compatibility

Is the panel builder's responsibility. The specifications for the switchgear must be observed.

Mounting Method

Built-in device plug-in technique

Overload current setting (Ir) - min

315 A

Amperage Rating

630 A

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

Handle type

Rocker lever

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard's requirements.

Short delay current setting (Isd) - min

630 A

Number of auxiliary contacts (normally closed contacts)

0

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard's requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard's requirements.

10.8 Connections for external conductors

Is the panel builder's responsibility.

Overload current setting (Ir) - max

630 A

Voltage rating

690 V - 690 V

10.9.2 Power-frequency electric strength

Is the panel builder's responsibility.

Degree of protection

IP20

Short delay current setting (Isd) - max

6300 A

Number of auxiliary contacts (change-over contacts)

0

Position of connection for main current circuit

Front side

10.7 Internal electrical circuits and connections

Is the panel builder's responsibility.

Features

Motor drive optional

Protection unit

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

Electrical connection type of main circuit

Screw connection

Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz

50 kA

10.9.3 Impulse withstand voltage

Is the panel builder's responsibility.

Number of poles

Three-pole

10.2.2 Corrosion resistance

Meets the product standard's requirements.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard's requirements.

10.2.7 Inscriptions

Meets the product standard's requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

Equipment heat dissipation, current-dependent

119.07 W

Number of auxiliary contacts (normally open contacts)

0

Instantaneous current setting (Ii) - min

1260 A

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder's responsibility.

10.3 Degree of protection of assemblies

Does not apply, since the entire switchgear needs to be evaluated.