Eaton Moeller series NZM - Molded Case Circuit Breaker. Circuit-breaker, 3p, 630A, plug-in module
Product Length/Depth
335 mm
Product Height
215.2 mm
Product Width
140 mm
Product Weight
7.72 kg
Compliances
RoHS conform
Rated operational current for specified heat dissipation (In)
630 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Instantaneous current setting (Ii) - max
6930 A
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
Built-in device plug-in technique
Overload current setting (Ir) - min
315 A
Amperage Rating
630 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Handle type
Rocker lever
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Short delay current setting (Isd) - min
630 A
Number of auxiliary contacts (normally closed contacts)
0
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
10.8 Connections for external conductors
Is the panel builder's responsibility.
Overload current setting (Ir) - max
630 A
Voltage rating
690 V - 690 V
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Degree of protection
IP20
Short delay current setting (Isd) - max
6300 A
Number of auxiliary contacts (change-over contacts)
0
Position of connection for main current circuit
Front side
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Features
Motor drive optional
Protection unit
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Electrical connection type of main circuit
Screw connection
Rated short-circuit breaking capacity Ics (IEC/EN 60947) at 400/415 V, 50/60 Hz
50 kA
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Three-pole
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Equipment heat dissipation, current-dependent
119.07 W
Number of auxiliary contacts (normally open contacts)
0
Instantaneous current setting (Ii) - min
1260 A
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.