Trade Price
£95.92
Per
1
Unit
EA
Pack Quantity
4



Neutral position
without neutral
Number of protected poles
3
Number of poles
3 P
Type of pole
3 P
Fixing mode
Din-Rail
Curve
C
Concurrently switching N-neutral
No
Number of modules
3
Top connection alignement for modular devices
Aligned terminal
Bottom connection alignement for modular devices
Aligned terminal
Rated short circuit breaking capacity Icn AC according IEC60898-1
10 kA
Rated operational voltage Ue
400 V
Type of supply voltage
AC
Rated insulation voltage
500 V
Rated impulse withstand voltage
6000 V
Minimum threshold voltage (Ue min)
12 V
Rated current
25 A
Rated service breaking capacity Ics AC according IEC 60898-1
7.5 kA
min/maxi threshold value of the AC thermal operation
1.13 / 1.45 In
Magnetic regulating currrent
5 / 10 In
min/maxi threshold value of the DC magnetic operation
7 / 15 In
min/maxi threshold value of the DC thermal operation
1.13 / 1.45 In
Rating current -10°C according to IEC 60947
35.44 A
Rating current -15°C according to IEC 60947
35.87 A
Rating current -20°C according to IEC 60947
36.3 A
Rating current -25°C according to IEC 60947
36.73 A
Rating current -5°C according to IEC 60947
35.01 A
Rating current 0°C according to IEC 60947
34.58 A
Rating current 10°C according to IEC 60947
33.72 A
Rating current 150°C according to IEC 60947
33.29 A
Rating current 20°C according to IEC 60947
32.86 A
Rating current 25°C according to IEC 60947
32.43 A
Rating current 30°C according to IEC 60947
32 A
Rating current 35°C according to IEC 60947
30.25 A
Rating current 40°C according to IEC 60947
28.5 A
Rating current 45°C according to IEC 60947
26.75 A
Rating current 5°C according to IEC 60947
34.15 A
Rating current 50°C according to IEC 60947
25 A
Rating current 55°C according to IEC 60947
23.25 A
Rating current 60°C according to IEC 60947
21.5 A
Rating current 65°C according to IEC 60947
19.75 A
Rating current 70°C according to IEC 60947
18 A
Rated short circuit breaking capacity Icn under 230V AC according IEC60898-1
10 kA
Rated short circuit breaking capacity Icn under 400V AC according IEC60898-1
10 kA
Rated ultimate short-circuit breaking capacity Icu under 230V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 240V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 400V AC IEC 60947-2
15 kA
Rated ultimate short-circuit breaking capacity Icu under 415V AC IEC 60947-2
15 kA
Rated short circuit breaking capacity Icn under 240V AC according IEC 60898-1
10 kA
Rated short circuit breaking capacity Icn under 415V AC according IEC 60898-1
10 kA
Rated ultimate short-circuit breaking capacity Icu under 220V AC IEC 60947-2
30 kA
Rated ultimate short-circuit breaking capacity Icu under 380V AC IEC 60947-2
15 kA
Rating current -25°C
32.08 A
Rating current -20°C
31.44 A
Rating current -15°C
30.79 A
Rating current -10°C
30.15 A
Rating current -5°C
29.51 A
Rating current 0°C
28.86 A
Rating current 5°C
28.22 A
Rating current 10°C
27.58 A
Rating current 25°C
25.64 A
Rating current 30°C
25 A
Rating current 35°C
24.36 A
Rating current 40°C
23.71 A
Rating current 45°C
23.07 A
Rating current 50°C
22.43 A
Rating current 55°C
21.78 A
Rating current 60°C
21.14 A
Rating current 65°C
20.49 A
Rating current 70°C
19.85 A
Correction factor of rating current for 2 devices placed side-by-side
1
Correction factor of rating current for 3 devices placed side-by-side
0.95
Correction factor of rating current for 4 and 5 devices placed side-by-side
0.9
Correction factor of rating current for 6 devices placed side-by-side
0.85
Correction factor of magnetic tripping with 100 Hz
1.1
Correction factor of magnetic tripping with 200 Hz
1.2
Correction factor of magnetic tripping with 400 Hz
1.5
Correction factor of magnetic tripping with 60