LC1DT80AG7

4P ELK CONT 80 A 120V50/60Hz

Trade Price

£372.70

Per

1

Unit

EA

Pack Quantity

1

LC1DT80AG7

Information

TeSys D contactor, 4 poles (4NO), for non-inductive load applications up to 80A/440V AC-1. They can be used to create motor starters for almost any type of application. It provides a 120V 60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by spring terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (70mm width), DIN-rail mounting or screw fixing. Power contacts have a 80A resistive load rating. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh). Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.76 inches wide and 4.72 inches deep. It weighs 2.54 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Technical Specifications

Range

TeSys TeSys Deca

Range of product

TeSys Deca

Product or component type

Contactor

Device short name

LC1D

contactor application

Resistive load

utilisation category

AC-1

Poles description

4P

[Ue] rated operational voltage

Power circuit: <= 690 V AC 25...400 Hz Power circuit: <= 300 V DC

[Ie] rated operational current

80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

[Uc] control circuit voltage

120 V AC 60 Hz

Compatibility code

LC1D

Pole contact composition

4 NO

Contact compatibility

M6

Protective cover

With

[Ith] conventional free air thermal current

10 A (at 60 °C) for signalling circuit 80 A (at 60 °C) for power circuit

Irms rated making capacity

140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 1000 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity

1000 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current

640 A 40 °C - 10 s for power circuit 900 A 40 °C - 1 s for power circuit 110 A 40 °C - 10 min for power circuit 260 A 40 °C - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit

Associated fuse rating

10 A gG for signalling circuit conforming to IEC 60947-5-1 125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit

Average impedance

1.6 mOhm - Ith 80 A 50 Hz for power circuit

Power dissipation per pole

10.2 W AC-1

[Ui] rated insulation voltage

Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Signalling circuit: 690 V conforming to IEC 60947-1 Signalling circuit: 600 V CSA certified Signalling circuit: 600 V UL certified Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category

III

Pollution degree

3

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability

6 Mcycles

Electrical durability

1.4 Mcycles 80 A AC-1 at Ue <= 440 V

Control circuit type

AC at 60 Hz

Coil technology

Without built-in suppressor module

Control circuit voltage limits

0.3...0.6 Uc (-40…70 °C):drop-out AC 60 Hz 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz 1...1.1 Uc (60…70 °C):operational AC 60 Hz

Inrush power in VA

140 VA 60 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA

13 VA 60 Hz cos phi 0.3 (at 20 °C)

Heat dissipation

4…5 W at 60 Hz

Operating time

4...19 ms opening 12...26 ms closi

Document Links

Datasheet

Technical Data