Trade Price
£741.84
Per
1
Unit
EA
Pack Quantity
1

TeSys Deca contactor, 4-pole (4NO), for non-inductive load applications up to 200A/1000V AC-1. It provides a 24V DC coil with transient suppressor module, power connection by screw connectors 2 inputs, control connection by screw clamp terminals. For operating rates until 1200 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (150mm width), mounting on 2 DIN-rails or screw fixing. Without build-in auxiliary contacts, side and front mounting auxiliary contact blocks available (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys
Range of product
TeSys Deca
Product or component type
Contactor
Device short name
LC1D
contactor application
Resistive load
utilisation category
AC-1 AC-3 AC-3e AC-4
Poles description
4P
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25...400 Hz Power circuit: <= 460 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
[Uc] control circuit voltage
24 V DC
Compatibility code
LC1D
Pole contact composition
4 NO
Contact compatibility
M8
Protective cover
With
[Ith] conventional free air thermal current
200 A (at 60 °C) for power circuit
Irms rated making capacity
1260 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
1100 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 40 °C - 10 min for power circuit 550 A 40 °C - 1 min for power circuit 950 A 40 °C - 10 s for power circuit 1100 A 40 °C - 1 s for power circuit
Associated fuse rating
250 A gG at <= 690 V coordination type 1 for power circuit 200 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
0.6 mOhm - Ith 200 A 50 Hz for power circuit
Power dissipation per pole
24 W AC-1
[Ui] rated insulation voltage
Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Power circuit: 1000 V conforming to IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability
8 Mcycles
Electrical durability
0.8 Mcycles 200 A AC-1 at Ue <= 440 V
Control circuit type
DC standard
Coil technology
With integral suppression device
Control circuit voltage limits
0.75...1.2 Uc (-40…55 °C):operational DC 0.15...0.4 Uc (-40…70 °C):drop-out DC 1...1.2 Uc (55…70 °C):operational DC
Inrush power in W
270…365 W (at 20 °C)
Hold-in power consumption in W
2.4…5.1 W at 20 °C
Operating time
20...35 ms closing 40...75 ms opening
Time constant
25 ms
Maximum operating rate
1200 cyc/h 60 °C
Connections - terminals
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end Power circuit: connector 1 10…120 mm² - cable stiffness: flexible without cable end Power circuit: connector 2 10…50 mm² - cable stiffness: flexible without cable end Power circuit: connector 1 10…120 mm² - cable stiffness: flexible with cable end Power circuit: connector 2 10…50 mm² - cable stiffness: flexible with cable end Power circuit: connector 1 10…120 mm² - cable stiffness: solid without cable end Power circuit: connector 2 10…50 mm²
Datasheet
Technical Data