TeSys F contactor, 3 poles (3NO), 780A/1000V AC-3, for motor applications up to 400kW@400V. Contactor with no coil to allow a later selection and installation (coil to be ordered separately), it provides bolt terminals for bars or cables with lugs. For high operating rates until 600 cycles/hour and environments until 55°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to a drawer for insertion of the selected coil and a large choice of add-on blocks and accessories (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Range
TeSys
Product name
TeSys F
Product or component type
Contactor
Device short name
LC1F
contactor application
Resistive load Motor control
utilisation category
AC-4 AC-3 AC-1
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz <= 460 V DC
[Ie] rated operational current
780 A (at <55 °C) at <= 440 V AC AC-3 1600 A (at <40 °C) at <= 440 V AC AC-1
Motor power kW
450 kW at 1000 V AC 50/60 Hz (AC-3) 400 kW at 380...400 V AC 50/60 Hz (AC-3) 425 kW at 415 V AC 50/60 Hz (AC-3) 425 kW at 440 V AC 50/60 Hz (AC-3) 450 kW at 500 V AC 50/60 Hz (AC-3) 220 kW at 220...240 V AC 50/60 Hz (AC-3) 475 kW at 660...690 V AC 50/60 Hz (AC-3) 110 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage
110...500 V AC 40...400 Hz with LX1/LX9 coil 48...440 V DC with LX4 coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
1600 A (at 40 °C)
Irms rated making capacity
7800 A AC conforming to IEC 60947-4-1
Rated breaking capacity
6240 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
3000 A 40 °C - 3 min 6250 A 40 °C - 10 s 5600 A 40 °C - 30 s 4600 A 40 °C - 1 min 2200 A 40 °C - 10 min
Associated fuse rating
800 A aM at <= 440 V 1600 A gG at <= 440 V
Average impedance
0.1 mOhm - Ith 1600 A 50 Hz
[Ui] rated insulation voltage
1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C
Power dissipation per pole
60 W AC-3 250 W AC-1
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil Drop-out: 0.2...0.4 Uc AC 40...400 Hz with LX1/LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.2...0.4 Uc DC with LX4 coil
Heat dissipation
22 W
Operating time
40...80 ms closing for with LX1/LX9 coil 130...230 ms opening for with LX1/LX9 coil 70...80 ms closing for with LX4 coil 100...130 ms opening for with LX4 coil
mounting support
Plate
standards
IEC 60947-1 IEC 60947-4-1 EN 60947-1 JIS C8201-4-1 EN 60947-4-1
product certifications
UL LROS (Lloyds register of shipping) RINA DNV CCC BV CB ABS UKCA
Connections - terminals
Power circuit: bar 2 cable(s) - busbar cross section: 100 x 5 mm Power circuit: bolted connection Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm² Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²
Tightening torque
Power circuit: 58 N.m Control circuit: 1.2 N.m
Mechanical durability
5 Mcycles
Inrush power in VA
1900…2300 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 1960…2420 VA (at 20 °C)with LX4 coil
Hold-in power consumption in VA
44…55 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil 42…52 VA (at 20 °C)with LX4 coil
Maximum operating rate
600 cyc/h 55 °C
Compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Protective t
Datasheet
Technical Data