Trade Price
£101.76
Per
1
Unit
EA
Pack Quantity
1

TeSys LR97D electronic overcurrent relay, 7A/690V, to be supplied with 100-120V AC, for protection of motors with a rated current 1.2-6A. It provides 3 dials to adjust the protection, LOAD (1.2-7A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when the current is higher than 3 x LOAD during more than 0.5sec in steady state and if there is a missing phase during more than 3sec. The settings include selectors for 1-phase/3-phase motors and manual/automatic reset, and the device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO/NC for fault signalling. Settings can be locked by sealing the transparent cover. For direct attachement to the bottom terminals of a 3-pole contactor LC1D09-D38, with screw clamp terminals on bottom, the separate mounting from the contactor is possible using the terminal block LAD7B106 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC, EAC), compliant RoHs/Reach.
Range
TeSys
Product name
TeSys D
Device short name
LR97
Product or component type
Electronic overcurrent relay
Relay application
Overload Imax > Isetting Locked rotor, mechanical jamming I > 3 x Isetting Sensitivity to phase failure
Product compatibility
LC1D09...D38
Network type
AC
[Us] rated supply voltage
100...120 V AC
Thermal protection adjustment range
1.2…7 A
[Ue] rated operational voltage
600 V AC 50/60 Hz for power circuit conforming to CSA 600 V AC 50/60 Hz for power circuit conforming to UL 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1
Quantity per set
Set of 10
Network frequency
50...60 Hz
Mounting support
Direct on contactor Rail
Tripping threshold
1.2...6 A
Surge withstand
6 kV conforming to IEC 61000-4-5
Contacts type and composition
1 C/O
[Ith] conventional free air thermal current
3 A for control circuit
Protection type
BS fuse 3 A - for control circuit GB2 circuit breaker 3 A - for control circuit GG fuse 3 A - for control circuit
Maximum power
28 W at 110 V DC conforming to IEC 60947 28 W at 220 V DC conforming to IEC 60947 55 W at 24 V DC conforming to IEC 60947 55 W at 48 V DC conforming to IEC 60947 140 VA at 48 V AC conforming to IEC 60947 360 VA at 110 V AC conforming to IEC 60947 360 VA at 220 V AC conforming to IEC 60947 70 VA at 24 V AC conforming to IEC 60947
[Ui] rated insulation voltage
Power circuit: 600 V conforming to CSA Power circuit: 600 V conforming to UL Power circuit: 690 V conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV
Phase failure sensitivity
< 3 s
Reset
Automatic reset 120 s fixed Electrical by interruption of power supply for minimum 0.1 s Manual reset
Time range
0.2...10 s - O-time knob 0.3...10 s - O-time knob 0.5..30 s - D-time knob
Signalling function
2 LEDs
Connections - terminals
Control circuit: cable 1 x 1…25 mm²flexible with cable end Control circuit: cable 1 x 1…25 mm²flexible without cable end Power circuit: cable 1 x 1…4 mm²flexible with cable end Power circuit: cable 1 x 1.5…10 mm²flexible without cable end Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end Control circuit: cable 2 x 1…25 mm²flexible with cable end Control circuit: cable 2 x 1…25 mm²flexible without cable end Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end Control circuit: lug-clamp 2 x 1…25 mm²flexible without cable end
Tightening torque
Control circuit: 0.6...1.2 N.m on lug-clamp Power circuit: 2 N.m on cable
height
67.5 mm
Width
45 mm
Depth
67.5 mm
Net weight
0.172 kg
standards
IEC 60947 IEC 60255-6
product certifications
GOST UL CSA
Protective treatme
Datasheet
Technical Data