Trade Price
POA
Per
1
Unit
EA
Pack Quantity
1

Range of product
Altivar Process ATV600
Product or component type
Variable speed drive
Product specific application
Process and utilities
Device short name
ATV630
Variant
Standard version
Product destination
Asynchronous motors Synchronous motors
EMC filter
Integrated with 25 m conforming to EN/IEC 61800-3 category C3
IP degree of protection
IP00 conforming to IEC 61800-5-1 IP00 conforming to IEC 60529 IP20 (with kit VW3A9705) conforming to IEC 61800-5-1 IP20 (with kit VW3A9705) conforming to IEC 60529
[Us] rated supply voltage
500...690 V - 15...10 %
Type of cooling
Forced convection
Supply frequency
50...60 Hz - 5...5 %
Motor power kW
7.5 kW at 500 V (normal duty) 5.5 kW at 500 V (heavy duty) 11 kW at 690 V (normal duty) 7.5 kW at 690 V (heavy duty)
Motor power hp
10 hp at 500 V normal duty 7.5 hp at 500 V heavy duty 15 hp at 690 V normal duty 10 hp at 690 V heavy duty
Line current
13.6 A at 500 V (normal duty) 14.7 A at 690 V (normal duty) 10.4 A at 500 V (heavy duty) 10.5 A at 690 V (heavy duty)
Prospective line Isc
70 kA
Apparent power
17.6 kVA at 690 V (normal duty) 12.5 kVA at 690 V (heavy duty)
Continuous output current
13.5 A at 4 kHz for normal duty 9.5 A at 4 kHz for heavy duty
Asynchronous motor control profile
Optimized torque mode Constant torque standard Variable torque standard
Synchronous motor control profile
Permanent magnet motor Synchronous reluctance motor
Speed drive output frequency
0.1…500 Hz
Nominal switching frequency
4 kHz
Switching frequency
2...8 kHz adjustable 4...8 kHz with derating factor
Safety function
STO (safe torque off) SIL 3
Discrete input logic
Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)
Communication port protocol
Ethernet Modbus serial Modbus TCP
Option card
Slot A: communication module, Profibus DP V1 Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink
Mounting mode
Wall mount
Maximum transient current
14.9 A during 60 s (normal duty) 14.3 A during 60 s (heavy duty)
Network number of phases
3 phases
Discrete output number
0
Discrete output type
Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A, R2C 30 V DC 5000 mA Relay outputs R3A, R3C 250 V AC 5000 mA Relay outputs R3A, R3C 30 V DC 5000 mA
Output voltage
<= power supply voltage
Permissible temporary current boost
1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty)
Motor slip compensation
Not available in permanent magnet motor law Automatic whatever the load Adjustable Can be suppressed
Acceleration and deceleration ramps
S, U or customized Linear adjustable separately from 0.01...9999 s
Physical interface
Ethernet 2-wire RS 485
Braking to standstill
By DC injection
Protection type
Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
Transmission rate
10, 100 Mbits 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Frequency re
Datasheet