ATV650C16N4F

FLOOR STANDING VSD IP54

Trade Price

POA

Per

1

Unit

EA

Pack Quantity

1

ATV650C16N4F

Information

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 440V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 160kW for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 132kW for applications requiring significant overload (up to 150%). It weighs 310kg and its dimensions are, 400mm wide, 2350mm high, 669mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on the floor. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.

Technical Specifications

Range of product

Altivar Process ATV600

Product or component type

Variable speed drive

Product specific application

Process and utilities

Device short name

ATV650

Variant

With disconnect switch

Product destination

Asynchronous motors Synchronous motors

EMC filter

Integrated with 150 m conforming to EN/IEC 61800-3 category C3

IP degree of protection

IP54 conforming to IEC 60529 IP54 conforming to IEC 61800-5-1

[Us] rated supply voltage

380...440 V - 15...10 %

Type of cooling

Forced convection

Supply frequency

50...60 Hz - 5...5 %

Motor power kW

160 kW (normal duty) 132 kW (heavy duty)

Line current

251 A at 400 V (heavy duty) 210 A at 380 V (normal duty) 291 A at 380 V (heavy duty) 244 A at 400 V (normal duty)

Prospective line Isc

50 kA

Apparent power

191 kVA at 440 V (normal duty) 160 kVA at 440 V (heavy duty)

Continuous output current

302 A at 2.5 kHz for normal duty 250 A at 2.5 kHz for heavy duty

Asynchronous motor control profile

Optimized torque mode Variable torque standard Variable torque standard

Synchronous motor control profile

Synchronous reluctance motor Permanent magnet motor

Speed drive output frequency

0.1…500 Hz

Nominal switching frequency

2.5 kHz

Switching frequency

2...8 kHz adjustable 2.5...8 kHz with derating factor

Safety function

STO (safe torque off) SIL 3

Discrete input logic

Positive logic (source) (DI1...DI8), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI8), > 16 V (state 0), < 10 V (state 1)

Communication port protocol

Modbus TCP Modbus serial Modbus serial

Option card

Slot A: communication module, PROFINET Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink Slot A: communication module, Profibus DP V1

Mounting mode

Floor-standing

Maximum transient current

332 A during 60 s (normal duty) 375 A during 60 s (heavy duty)

Network number of phases

3 phases

Discrete output number

0

Discrete output type

Relay outputs R1A, R1B, R1C 250 V AC 3000 mA Relay outputs R1A, R1B, R1C 30 V DC 3000 mA Relay outputs R2A, R2C 250 V AC 5000 mA Relay outputs R2A,

Document Links

Datasheet