Trade Price
£7,902.19
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER SACE EMAX2 E2.2S 1250 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/DIP-LSI R 1250 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 79.1 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
2ee70869-025a-4d0c-9935-cb7d47f9b073 Italy (IT)
Simplified SCIP
eac95414-1b63-4d51-8abc-2f36c49a09a7 Poland (PL)cac41eb9-f5d0-47f0-bd5e-c41ebcdd76b6 Hungary (HU)e0abeb9e-824c-4501-a8b7-11400e74a4fd Hungary (HU)371cbce2-c992-45f5-a285-d14239adb366 Norway (NO)2057308f-250c-4666-9c54-32ffccfe6308 Bulgaria (BG)51bb4090-62a6-433c-be20-46d36fb87ec3 Germany (DE)be393fea-f0bd-469d-897b-a76c141e13c2 Germany (DE)f91cf77e-e2c1-4ec0-b502-01963b095f19 Croatia (HR)1b3061af-6eeb-4c70-a98d-c0ab3f627cc7 Denmark (DK)8c66d7b0-05da-4c8e-b345-cd725198ad9a Germany (DE)11331793-cd67-4753-92f7-1ddb9f0459e4 Germany (DE)b0016fb0-ce54-4c48-b4f7-f97be4ad4c46 Belgium (BE)5a47d709-2784-49fc-aaa3-5e84321591bb Sweden (SE)27203d0a-3491-44e9-b944-88b2a2441a05 Netherlands (NL)293f3289-a742-4511-a227-37416d510c6a Estonia (EE)42fd5712-015c-4a90-b190-7f5107ef3196 France (FR)2c013091-c804-4ff0-9a40-66c092f06e27 Greece (GR)1fcf4712-1766-48b4-a772-404810382774 Finland (FI)056cd37f-9ec5-4a86-afa4-80cbae1b78c0 Poland (PL)5e80f2ff-506d-4885-ad43-a41be7d06f97 France (FR)1f3c5016-9a2a-4f67-9ddb-78b8681e4351 Belgium (BE)852e6da1-7209-44e6-880c-30233b3b6314 Spain (ES)8fd68019-10a7-4fec-82ab-90ea399a5ff1 Portugal (PT)91aa1993-40c4-4061-87be-5e7d4e433cde Sweden (SE)0ee1f087-22d0-4f39-a08d-d66894c904db Czech Republic (CZ)96154b2f-1b6f-4c33-8062-9202be82a327 Poland (PL)
Order Code US and Canada
ZBSREHBB000A000000XX
EAN
8015644754426
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
366 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
53 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
615 mm
Package Level 1 Gross Weight
58 kg
Package Level 1 EAN
8015644754426
Current Type
AC
Electrical Durability
Ue =< 440 V 15000 cycleUe = 500 ... 690 V 15000 cycle30 cycles per hour
Mechanical Durability
25000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
100 %
Number of Poles
4
Power Loss
83 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
1250 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 85 kA(230 V AC) 85 kA(380 V AC) 85 kA(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(660 V AC) 66 kA(690 V AC) 66 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 66 kAfor 3 s 50 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 85 kA(415 V AC) 85 kA(440 V AC) 85 kA(500 V AC) 66 kA(525 V AC) 66 kA(690 V AC) 66 kA
Rated Uninterrupted Current (Iu)
1250 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Dip LSI
Release Type
EL
Short-Circuit Performance Level
S
Standards
IEC
Sub-type
E2.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
IDEA Granular Category Code (IGCC)
4926 >> Air circuit breakers
Object Classification Code
Q
UNSPSC
39121615
WEEE Category
5. Small Equipment (No External Dimension More Than 50 cm)
eClass
V11.1 : 27370409