Trade Price
£27,492.36
Per
1
Unit
EA
Pack Quantity
1
C.BREAKER EMAX2 E6.2H 4000 FIXED FOUR-POLE WITH TERMINALS REAR HORIZONTAL AND SOLID-STATE RELEASE IN AC EKIP/TOUCH-LSIG R 4000 FITTED WITH: 4 AUXILIARY CONTACT AND C.BREAKER IN POSITION OPEN-CLOSED
ABB EcoSolutions
Yes
Circular Design Principles Recyclability Rate
Design for Closing Resource Loops - Standard EN45555 - 77 %
Group Waste to Landfill Target
UL 2799 Zero Waste To Landfill Validation available
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
SCIP
fd46707c-ec22-4722-add4-bcb6e8c4368b Italy (IT)
Simplified SCIP
55234862-09fd-4d70-ae07-66606b210685 Germany (DE)870ddeca-f958-425b-89e8-8145feab45d0 Sweden (SE)383e2b14-b95e-46cb-8105-c5c42a5a126a Poland (PL)01c1335e-f6fa-4ba0-b379-950f145c7c7c Czech Republic (CZ)27f75f29-1d87-472e-8ca1-ab13a9251379 Poland (PL)434b54ab-5ecd-4192-9674-e67912e836a1 Norway (NO)790da2ee-063c-4cba-a3de-4d47423b75ff France (FR)ada25cdc-2025-41df-96eb-482a12ae9c8a Finland (FI)74e5f84b-9bf1-4fde-b1f7-bfc4e1fe741d Belgium (BE)583fddd4-9038-44ad-8cd8-24c0a95dd61b Croatia (HR)e0e7cc62-624e-42d2-a6ee-6bf101452f38 Hungary (HU)2833cd64-35d5-482d-ae2a-dca30fdedfce Estonia (EE)ab69e476-9a22-4429-b88c-939212121692 Denmark (DK)b47e87f8-9f84-4aea-b627-4b3e1becdf93 Greece (GR)67aedbbc-627e-47a8-a10d-0018287b9d41 Germany (DE)b14eaab5-0517-46d1-b529-5b04f3b8c878 France (FR)7de56b2a-4e6b-4be1-aa1b-11f58c896644 Germany (DE)9f884bc5-824a-411b-a5dd-ad71f888ee62 Sweden (SE)adb0dd0f-97f2-4545-b964-743649b29126 Netherlands (NL)dcc56d8b-b77d-4ea3-9782-5d05a6250871 Poland (PL)60f356f3-ae3a-4b1a-9610-32e9f8acaab4 Belgium (BE)647c3eff-ba06-4781-943d-8cd320807c62 Spain (ES)91c6a20b-bdf8-452d-8365-79f777dfd308 Germany (DE)836fcfcf-ec6d-4957-ad90-e7496212a58b Hungary (HU)13e2ae2a-57da-45ae-be85-b967cf46f671 Portugal (PT)6c7ad957-1730-4e71-9e11-ec594f3df679 Bulgaria (BG)
Order Code US and Canada
ZDHWERBF000A000000XX
EAN
8015644757168
Minimum Order Quantity
1 piece
Customs Tariff Number
85362090
Product Net Width
888 mm
Product Net Height
371 mm
Product Net Depth / Length
270 mm
Product Net Weight
125 kg
Package Level 1 Units
box 1 piece
Package Level 1 Width
515 mm
Package Level 1 Height
610 mm
Package Level 1 Depth / Length
1127 mm
Package Level 1 Gross Weight
134 kg
Package Level 1 EAN
8015644757168
Current Type
AC
Electrical Durability
Ue =< 440 V 4000 cycleUe = 500 ... 690 V 4000 cycle10 cycles per hour
Mechanical Durability
12000 cycle60 cycles per hour
Neutral Pole Current ([%Iu])
50 %
Number of Poles
4
Power Loss
309 W
Product Main Type
SACE Emax 2
Product Name
Air Circuit Breaker
Product Type
Air Circuit Breaker
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)
100 %
Rated Current (In)
4000 A
Rated Voltage (Ur)
690 V
Rated Impulse Withstand Voltage (Uimp)
acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui)
AC 1000 V
Rated Operational Voltage
690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics)
(220 V AC) 100 kA(230 V AC) 100 kA(380 V AC) 100 kA(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(660 V AC) 100 kA(690 V AC) 100 kA
Rated Short-time Withstand Current Low Voltage (Icw)
for 1 s 100 kAfor 3 s 100 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)
(400 V AC) 100 kA(415 V AC) 100 kA(440 V AC) 100 kA(500 V AC) 100 kA(525 V AC) 100 kA(690 V AC) 100 kA
Rated Uninterrupted Current (Iu)
4000 A
Recommended Screw Driver
Main Circuit M12
Release
Ekip Touch LSIG
Release Type
EL
Short-Circuit Performance Level
H
Standards
IEC
Sub-type
E6.2
Terminal Connection Type
Rear flat Horizontal
Terminal Type
Bolt
Tightening Torque
70 N·m
Version
F
ETIM 7
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 8
EC000228 - Power circuit-breaker for trafo/generator/installation protection
ETIM 9
EC000228 - Power circuit-breaker for trafo/generator/installation protection
Object Classification Code
Q
WEEE Category
4. Large Equipment (Any External Dimension More Than 50 cm)
eClass
V11.1 : 27370409
Datasheet